| Danfoss CTI 100, Circuit breakers with built-in current limiter
The Danfoss CTI product range is modular, flexible and offers a large selection of clip-on auxiliary functions and accessories: Aux. contacts, alarm contacts, voltage- and under-voltage trips.
• Compact design • DIN rail mounting • Motor application • Short-circuit protection • Overload protection of motors (31.5 - 45 kW) • Setting range: 40 - 90A • Operation switch (manual motor starter) • Isolation switch (with locking device) • Emergency switch (with undervoltage trip) • Indications: • Test and reset functions • ON or OFF • Thermal and electromagnetic trip
Features • Overload protection and short circuit protection of motor installations. • Test function for thermal trip • Manual reset function • Indication for thermal trip • Indication for magnetic trip (short circuiting) • Single phase protection (Differential trip) • Temperature compensated (-20 0C to + 60 0C) • Tripping class 10
Approvals GL-Germanischer Lloyd Current limiter, CTL 65 GL-Germanischer Lloyd Circuit breaker, CTI 25 UL-Underwriters Laboratories inc. Circuit breaker, CTI 16T;CTI 20TB;CTI 25M;CTI 25MB;CTI 25S;CTI 25SB;CTI 32TB;CTI 45MB;CTI 45SB
Code number selection Code no. Type Current range (A) Max load AC-3 (kW) Max trip current (A) Breaking cap.Ics 380-415V 047B3002 CTI 100 63,00 - 90,00 A 45,00 kW 1.260,0 A 25 kA 047B3014 CTI 100 40,00 - 63,00 A 31,50 kW 882,0 A 50 kA 047B3015 CTI 100 63,00 - 90,00 A 45,00 kW 1.260,0 A 25 kA