The Danfoss MBT 9110 temperature transmitter can be used for converting the Pt100 ohm signal or the thermo couple mV signal to a 4 to 20 mA signal. The MBT 9110 can be used together with all types of MBT sensors, Pt100 as well as Thermo couple.
MBT 9110 transmitters in the standard program are delivered in an enclosure, but are also used as an integrated part of certain temperature sensors.
The transmitter is available as standard or galvanic isolated with or without EEx approval.

• 2, 3 or 4-wire universal transmitter for industrial and marine applications
• Pt100 or thermocouple input
• 4 - 20 mA standard output signal - with or without galvanic isolation
• Available with EEX ia IIC T4 / T6 approvals
• For mounting in DIN B connection head or in a separate enclosure
• Advanced sensor fault indication
• Temperature linearized
• Available with all relevant marine approvals
Flexibility is the key word
The MBT 9110 can be programmed by computer to convert Pt100, Pt1000 and the common thermocouple types to a 4 to 20 mA signal. It is also possible to program a sensor error or cable resistance into the transmitter and thereby automatically compensate the error. High measuring accuracy
The MBT 9110 has an extremely high measuring accuracy and this insures reliable measurement every time.
Suitable for EEx applications
MBT 9110 complies with Eex ia II C T1 ...T6.
Low sensibility towards electronic noise.
If needed, the MBT 9110 can be delivered with galvanic isolation. This is recommended when measuring with Thermocouples. Generally the MBT 9110 is resistant against influence from EMC and meets the requirements of EN 50081-1 and EN 50081-2.
Compensation of wire resistance
When using cables to transfer the signal from a Pt100 element, the resistance of the wires will give a measurement error.
The MBT 9110 automatically eliminates wire resistance errors by using 3 or 4-wire compensation. This is an advantage in situations where the transmitter cannot be placed near the sensor.
Multiple mounting methods
Flexibility is also a key word when mounting the MBT 9110.
The transmitter can be mounted on a DIN-rail, in a separate box or integrated in for example the MBT 5252.
Integrating the transmitter in the sensor ensures a reliable transfer of the measuring values to the controller.
Approvals
BV-Bureau Veritas Temperature transmitter, MBT 9110
BV-Bureau Veritas Temperature transmitter, MBT 9110
Danfoss-foss - Danfoss Temperature transmitter, MBT
DEMKO-KO - UL International Demko A/S Temperature transmitter, MBT 9110
DNV-Det Norske Veritas Temperature transmitter, MBT 9110
DNV-Det Norske Veritas Temperature transmitter, MBT 5560
GL-Germanischer Lloyd Temperature transmitter, MBT 9110 551 KB
KEMA-A - N.V. tot Keuring van Electrotechnische Materialen Temperature transmitter, MBT 9110
LR-Lloyds Register of Shipping Temperature transmitter, MBT 9110
LR-Lloyds Register of Shipping Temperature transmitter, MBT 9110
NKK-Nippon Kaiji Kyokai Temperature transmitter, MBT 9110
Code number selection
Code no. Type Resistance Thermocouple Temp. Transm.setting Transm. IP
value range[°C] range[°C] type
084Z3108 MBT 9110 1 x Pt 100 - -200 - 850 °C -50 - 100 °C Standard IP 68/IP 00
084Z3125 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 100 °C Standard EEx IP 68/IP 00
084Z3155 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 160 °C Standard EEx, high lid IP 54
084Z5114 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 150 °C Standard IP 68/IP 00
084Z5185 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 200 °C Standard in box IP 54
084Z5187 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 150 °C Standard, high lid IP 54
084Z5190 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 100 °C Standard IP 68/IP 00
084Z6000 MBT 9110 1 x Pt 100 - -200 - 850 °C -50 - 200 °C Standard, high lid IP 54
084Z6135 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 600 °C Standard in box IP 54
084Z6202 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 120 °C Standard IP 68/IP 00
084Z6207 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 600 °C Standard, high lid IP 54
084Z8115 MBT 9110 1 x Pt 100 - -200 - 850 °C -50 - 50 °C Standard in box IP 54
084Z8116 MBT 9110 1 x Pt 100 - -200 - 850 °C -10 - 40 °C Standard in box IP 54
084Z8117 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 100 °C Standard in box IP 54
084Z8118 MBT 9110 1 x Pt 100 - -200 - 850 °C -10 - 150 °C Standard in box IP 54
084Z8119 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 250 °C Standard in box IP 54
084Z8120 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 400 °C Standard in box IP 54
084Z8121 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 150 °C Standard in box IP 54
084Z8123 MBT 9110 1 x Pt 100 - -200 - 850 °C -10 - 40 °C Galv. isolated in box IP 54
084Z8124 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 100 °C Galv. isolated in box IP 54
084Z8125 MBT 9110 1 x Pt 100 - -200 - 850 °C -10 - 150 °C Galv. isolated in box IP 54
084Z8129 MBT 9110 - (1) -180 - 1372 °C 0 - 600 °C Galv. isolated in box IP 54
084Z8130 MBT 9110 - (1) -180 - 1372 °C 0 - 800 °C Galv. isolated in box IP 54
084Z8140 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 200 °C Standard IP 68/IP 00
084Z8243 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 200 °C Galv. isolated IP 68/IP 00
084Z8295 MBT 9110 1 x Pt 100 - -200 - 850 °C 0 - 600 °C Standard IP 68/IP 00
Note (1) 1 x NiCr-Ni, Type K